Chapter 13 Sprayed Fire Resistant Materials

(929 m2) or part thereof of the sprayed area in each story.

NCSBC-1704.11.5.2 Structural framing members. The test samples for determining the cohesive/adhesive bond strength of the sprayed fire-resistant materials shall be selected from beams, girders, joists, trusses and columns at the rate of not less than one sample for each type of structural framing member for each 10,000 square feet (929 m2) of floor area or part thereof in each story.

SICC-1304 COMPLETION OF SPRAYED FIRE-RESISTANT MATERIALS

Upon completion of sprayed fire-resistant material construction, the SIER shall, after review and approval by the AR and SER, submit a completion letter to CCBSD. The SIER shall also indicate the date of completion on the final report of special inspections for sprayed fire resistance materials.