Valve Sample 11 ASCO Catalog No. NSEL830081F

BASELINE TESTING VALVE SAMPLE NO. 11A ASCO CATALOG NO. NSEL830081F TESTING CONDUCTED IN ACCORDANCE WITH QUALIFICATION SPECIFICATION AQS 21691 REV 3 & ASCO TEST PROCEDURE BULLETIN TP-3-046 TEST MEDIUM: AIR

INITIAL

POST

POST

POST

POST

POST ENVI.

WEAR

RADIATIO

SEISMIC

RADIATION

DBE

AGING

N AGING

DBE

DBE

passed

passed

passed

passed

Note 1 end cap

110cc/min

20cc/min

30cc/min

10cc/min

20cc/min

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

passed

passed

passed

passed

passed

EXTERNAL LEAKAGE @_10 & 150 PSIG (ENERGIZED & DE-ENERGIZED)

OPERATIONAL:_10X @ 150 PSIG 150 TO 0 PSIG

SEAT LEAKAGE HIGH PRESSURE

@

150

PSIG

ENERGIZED ALLOW: 1.5scfh

DE-ENERGIZED ALLOW: 1.5scfhn

SEAT LEAKAGE HIGH PRESSURE

@

10

PSIG

ENERGIZED ALLOW: 1.5scfh

DE-ENERGIZED ALLOW: 1.5scfhn

passed

passed

passed

passed

passed

.26sec

.26sec

.24sec

.28sec

.30sec

.68sec

.74sec

.68sec

.69sec

.78sec

Note 1: External leakage detected at end cap gasket – leakage was not enough to affect performance of valve.

Based on the performance of 11B and 11C, valve 11C is considered qualified.