Baseline Testing Valve Sample 11B ASCO Catalog No. NSEL830081F

BASELINE TESTING VALVE SAMPLE NO. 11B ASCO CATALOG NO. NSEL830081F TESTING CONDUCTED IN ACCORDANCE WITH QUALIFICATION SPECIFICATION AQS 21691 REV 3 & ASCO TEST PROCEDURE BULLETIN TP-3-046 TEST MEDIUM: AIR

passed

passed

passed

passed

SBSA

SBSA end cap

Note 3

35cc/min

.35scfh

110cc/min

30cc/min

30cc/min

15cc/min

35cc/min

10cc/min

10cc/min

30cc/min

20cc/min

10cc/min

0

0

0

0

0

0

0

0

0

0

0

0

passed

passed

passed

passed

passed

passed 150-35psi

passed

passed

passed

passed

passed

passed

.26sec

.26sec

.22sec

.26sec

.28sec

.26sec

.68sec

.68sec

.64sec

.68sec

.76sec

.76sec

Performance Summary: During Environmental DBE Simulation, Valve was energized to perform cycle 12. Valve failed to operate Ref. SOA 013). Post Environmental DBE was performed using a replacement coil and bypassing the p ower reduction module. Valve was acceptable.

POST

POST

POST

POST

POST ENVI.

WEAR

RADIATION

SEISMIC

RADIATION

DBE

AGING

AGING

DBE

DBE

SEAT LEAKAGE

ENERGIZED

HIGH PRESSURE

ALLOW: 1.5scfh

EXTERNAL LEAKAGE @_10 & 150 PSIG (ENERGIZED & DE-ENERGIZED)

OPERATIONAL:_10X @ 150 PSIG 150 TO 0 PSIG

INITIAL

NOISE TEST

SEAT LEAKAGE HIGH PRESSURE

@

150

PSIG

ENERGIZED ALLOW: 1.5scfh

DE-ENERGIZED ALLOW: 1.5scfhn

@

10

PSIG

DE-ENERGIZED ALLOW: 1.5scfhn

SHIFT TIME

FILL @__150__PSIG

DISCHARGE @ 150 PSIG

Note 3: External leakage detected at end cap/body and SBSA/body joint. Leakage is not significant enough to affect performance of the valve.