X hits on this document

PDF document

ADVISORY BOARD CALENDAR - page 18 / 20

47 views

0 shares

0 downloads

0 comments

18 / 20

ADVISORY BOARD CALENDAR

May 19, 2004

Calendar # Submission # Applicant Name and Address

Type of Request

Installation Location

Status

Fee

45701

  • ………

    .

Zwicker Electric Co., Inc. 200 Park Avenue South

New York

NY

10003

Requesting permission in an 274 unit apartment building not to install floor outlet receptacles in front of a corner glass wall, other receptacles will be installed on the other walls at a distance greater than 12 feet on center in 72 living rooms.

325 North End Avenue

New York

NY

Approved

$0.00

45702

…………

Joseph R. Loring & Associates, Inc.

21 Penn Plaza, 14th Floor

New York

NY

10001

Requesting permission to install the receptacle outlet spacing as per the old New York City Electrical Code in a dormitory that was designed in 2002 and filed by the electrical contractor in August of 2003.

Brooklyn Law School

Brooklyn

NY

Approved

$0.00

45703

  • ………………

    .

J.J. Rosenberg Electrical Contrs, Inc.

27 Herkimer Place

Brooklyn

NY

11216

Requesting concept approval to install secondary power to a fire pump located in 320 West 66th Street, New York. By tapping the line side of service in a adjoining building at 125 West End Ave, both buildings are under one ownership and upgrading the existing generator will create building reinforcement hardships.

20 W. 66th St. and 125 West End Av

New York

NY

Denied

$0.00

Article 695.3 (c ) of New York City's Amendments to the 2002 National Electrical Code states: ( c) Multiple Independent Sources. Two or more feeder sources to the building arranged to independently operated may permitted, as approved by the Commissioner of Buildings, where reliability of the sources can be demonstrated.

45704

……………… …………….

Diane Electric, Inc. 1371 Seabury Avenue

Bronx

NY

10461

Requesting permission to install a 3 phase 100 amp 250 volt service switch fused at 60 amps in lieu of a fuse cutout to power a fire alarm system. The 100 amp service switch will be painted red and labeled as

Verizon 230 West 36th Street

New York

NY

Approved

$0.00

fire service and be locked on the "on" position with a fireman's lock. The switch will be installed within 5 feet of the service equipment.

Wednesday, March 18, 2009

Page 18 of 20

Document info
Document views47
Page views47
Page last viewedFri Dec 02 18:57:19 UTC 2016
Pages20
Paragraphs1378
Words5136

Comments