Instrumentation and Completing the System: The AFG Flow Grid is not a complete measuring system. To com- plete the system it is necessary to convert the output signal into a more useful form.

For occasional checking of the AFG Flow Grid, differential pressure portable instruments may be used.

A pressure transmitter may be used to give an electrical output proportional to the pressure signal or include a square rooting function to indicate velocity directly.

If the AFG Flow Grid is to be used as part of an alarm system, to warn for example, if the volume flow rate drops below a certain limit, a manometer fitted with alarm trips may be used.

To complete the installation, fit flexible tubing from the elbows at the ends of the AFG Flow Grid to the chosen instrument. The elbow connector is 6 mm outside diameter.

Interpretation of Output: Duct mean velocity: The differential pressure signal obtained across the output tap- pings of the AFG Flow Grid is proportional to the duct mean veloc- ity pressure and to the square of the duct mean velocity.

The relationship between the differential pressure and the velocity pressure is the magnification factor M.

M= (ΔP)/(Pû)

AFG Flow Grid: M=1.0 Table 3: Calculating Velocity from Differential Pressure

Volume Flow Rate: The most useful information obtainable from an AFG Flow Grid is the volume flow rate in the duct in which it is fitted.

Table 4: Calculating Volumetric Flow from Differential Pressure

page 4

Fig. 14: Typical Performance Graphs

DUCT MEAN VELOCITY v ft/min

1000

2000

3000

4000

500

2.0

FlowGRID DIFFERENTIAL PRESSURE p Pa

400

300

200

5/8˝ (16 mm)

5/16˝ (6 mm) Tube

1.5

1.0

0.5

FLOWGRID DIFFERENTIAL PRESSURE P IN Wg.

100

0

0

5

10 DUCT MEAN VELOCITY m/s

15

20

0

Fig. 14 (above) shows AFG Flow Grid differential pressure against duct mean velocity.

This graph is drawn for standard air conditions of 1.2 kgs/m3 (0.075 lbs/ft3) and may be used if lower levels of accuracy (See page 1 & 3) are acceptable. If higher levels of accuracy are required on site calibration is essential (See next page).

Losses: Introducing an AFG Flow Grid into a duct causes a very small pres- sure loss, which should be known when calculating the energy requirements in a ducted system. The loss is measured as the pressure drop between tapping points situated D/2 upstream and downstream of the grid.

Fig. 15 shows magnification factor M and pressure loss factor L plotted against mean velocity for a typical AFG Flow Grid installa- tion. It will be seen that these values remain sensibly constant over the useful range of the AFG Flow Grid.

Fig. 15: Magnification and Pressure Loss Factors