Obstruction Right Angle Bend Radius Angle Bend r=1D or less Opposed Blade Damper 30° Bend Tapered Contraction Sudden Contraction

±10% 10.0D 10.0D

±15% 3.5D 3.5D

10.0D 3.5D 3.5D 3.5D

3.5D 2.0D 2.0D 2.0D

Fig. 16

page 6

Table 10: Uncertainty and Repeatability of Measurement Expected uncertainty of measurement with typical system obstruc- tions:

Straight Upstream Length

Required to Maintain

Note: For rectangular ducts D= Width + Height of Duct/2

On any particular installation repeatability of signal output is likely to be better than ±5%.

When calibrated on site (See Previous Page) uncertainty of mea- surement is likely to be better than ±5%.

MAINTENANCE No maintenance is normally required except where a high dust burden is likely to be encountered in the air stream. Deposits in the pressure holes will affect calibration and it is advisable to provide some means of access for cleaning when installing the AFG Flow Grid. The Series AFG Flow Grid is not field serviceable and should be returned if repair is needed (field repair should not be attempt- ed and may void warranty). Be sure to include a brief description of the problem plus any relevant application notes. Contact cus- tomer service to receive a return goods authorization number before shipping.

Fig. 17

©Copyright 2005 Dwyer Instruments, Inc.

Printed in U.S.A. 12/05

FR# R1-443394-00

DWYER INSTRUMENTS, INC.

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A.

Phone: 219/879-8000 Fax: 219/872-9057

www.dwyer-inst.com e-mail: info@dwyer-inst.com

Document info
Document views17
Page views17
Page last viewedThu Dec 08 16:14:48 UTC 2016
Pages6
Paragraphs361
Words2505

Comments