Power Control Center

Features of the Power Control Center The features of the Power Control Center (PCC) modules make them equivalent to a conventional housing/building: The degree of protection of the switchgear rooms is IP 54. The switchgear room temperature in the PCC modules is controlled between 10 °C and 35 °C by air-conditioning units. At least one redundant air- conditioning aggregate is provided. The air is cleaned by a filter. The sealed construction prevents any ingress of moisture or dust by leakage. In addition, the heat exchangers dehydrate the replacement air so that condensation inside the modules cannot occur.