TeSys thermal overload relays

Setting range

Fuse rating

Reference

A 0.11-0.16 0.16-0.23 0.23-0.36 0.36-0.54 0.54-0.8 0.8-1.2 1.2-1.8 1.8-2.6 2.6-3.7 3.7-5.5 5.5-8.0 8.0-11.5

BS88 (2) 2 2 2 4 4 6 6 10 16 16 20 20/35

TEXLR2K0301 TEXLR2K0302 TEXLR2K0303 TEXLR2K0304 TEXLR2K0305 TEXLR2K0306 TEXLR2K0307 TEXLR2K0308 TEXLR2K0310 TEXLR2K0312 TEXLR2K0314 TEXLR2K0316

For TEXLE1 and LE2GBK series Direct-On-Line starters With test button, tripped indication, sealable tamperproof cover

Motor rating- 3Ph 415V (1)

kW

A

0.37

1

0.55

1.5

0.75/1.1

1.9/2.5

1.5

3.4

2.2

4.8

3

6.3

4/5.5

8.1/10.9

Motor rating- 3Ph 415V (1)

Setting range

Fuse rating

Reference

kW

A

A 0.10-0.16 0.16-0.25 0.25-0.40 0.40-0.63 0.63-1.0 1.0-1.7 1.6-2.5 2.5-4.0 4.0-6.0 5.5-8.0 7.0-10.0 9.0-13.0 12.0-18.0 16.0-24.0

BS88 (2)

LRD01 LRD02 LRD03 LRD04 LRD05 LRD06 LRD07 LRD08 TEXLRD10 TEXLRD12 TEXLRD14 TEXLRD16 TEXLRD21 TEXLRD22

0.37 0.55 0.75 1.1/1.5 2.2 3 4 5.5 7.5 11

0.98 1.4 2 2.5/3.5 5 6.5 8.4 11 14.8 21

6 10 16 16 20 20 25 35 50

For TEXLE1 and LE2GBT series Direct-On-Line starters With test button, tripped indication, sealable tamperproof cover

Setting range

Fuse rating

Reference

A 7.0-10.0 9.0-13.0 12.0-18.0 16.0-24.0 16.0-24.0

BS88 (2) 25 35 40 50 50

TEXLRD14 TEXLRD16 TEXLRD21 TEXLRD22 TEXLRD22

For TEXLE3GBT series Star/Delta starters With test button, tripped indication, sealable tamperproof cover

  • (1)

    Values indicated are standard motor power ratings and average operational full load currents

  • (2)

    gM fuses may be used

  • (3)

    Set Star / Delta overload relay at 0.58 x Motor FLC (Full Load Current)

    • Products are from the standard Telemecanique range and complement the T-Express offer

Motor rating- 3Ph 415V (1)

kW

FLC A (3)

7.5

14

11

21

15

28

18.5

35

22

40

Power & control

3 pole contactors

Rev Contactor

reference (1)

LC2K0601U7

LC2K0901U7

LC2K1201U7

AC3 rating- 3Ph

Rated op power Coil

Contactor

415V A

415V AC3 kW

Voltage

reference

3 pole contactors and reversing contactors screw clamp terminals

May be used with TEXLR2K overload relays

240V AC

LC1K0610U7

240V AC

LC1K0910U7

240V AC

LC1K1210U7

AC1 rating

Coil

Contactor

415V A

Voltage

reference (1)

20

240V AC

LC1K09004U7

4 pole contactors

screw clamp terminals

6

2.2

9

4

12

5.5

4 pole contactors

Reference

LA1KN20

LA1KN22

LA1KN11

LA1KN40

Contact attachments clip onto top or side of contactor

Rating Ith A

10 10 10 10

Contacts 2NO

2NO + 2NC

1NO + 1NC

4NO

Plug-in relays

Contacts 2 changeover

Reference TEXR2P7

2 changeover

TEXR2F7

2 changeover

TEXR2B7

3 changeover

TEXR3P7

3 changeover

TEXR3F7

3 changeover

TEXR3B7

Plug-in relays with test button

  • 8 or 11 pin octal type in 230V, 110V or 24V

  • High quality replacement for most Octal type relays

Rating Ith A

8pin 230VAC relay and base

8pin 110VAC relay and base

8pin 24VAC relay and base

11pin 230VAC relay and base

11pin 110VAC relay and base

11pin 24VAC relay and base

  • Test facility

Function

Time range

Width

Reference

Multi function timer up to 300 hour

Up to 300 Hour

22.5mm

TEXTIM1

Delay on timer 0.3-30S

0.3- 30 Sec

22.5mm

TEXTIM2

Electronic timer 24AC/DC and 110-230 VAC

  • Multi- voltage - 24VAC/DC-/110-230VAC

  • Multi- function type- 5 functions with timing up to 300 hours

Terminal assemblies

Description

Reference

10way +E 2.5 sq mm terminal strip fitted on 100mm length DIN rail

TEXAB110

Terminal assemblies

  • (1)

    Includes mechanical interlock

    • Products are from the standard Telemecanique range and complement the T-Express offer