PowerControl / PowerAssist Integrated Transfer switch AC inputs (2x) AC feed through capacity (A)

Input voltage range (V DC) Output (pure sinewave) Cont. output power at 77ºF/25°C (VA) (5) Cont. output power at 77ºF/25°C (W) Cont. output power at 100ºF/40°C (W) Peak power (W) Maximum efficiency (%) Zero-load power (W) Load shedding output

Charge voltage 'absorption' (V DC) Charge voltage 'float' (V DC) Storage mode (V DC) Charge current house battery (A) (4) Charge current starter battery (A) Battery temperature sensor

Multi purpose relay (6) Protection (2) Common Characteristics

Common Characteristics Battery-connection 120/240 V AC-connection Weight Dimensions (hxwxd)

Safety Emission Immunity

  • 1)

    Can be adjusted to 50 Hz

  • 2)

    Protection

    • a)

      Output short circuit

    • b)

      Overload

    • c)

      Battery voltage too high

    • d)

      Battery voltage too low

    • e)

      120VAC on inverter output

    • f)

      Input voltage ripple too high

12/5000/200

24/5000/120

48/5000/70

120/240V

120/240V

120/240V

Yes

Yes

Yes

Yes

Yes

Yes

Input voltage: 120 V or 120/240 V

Input frequency: 45 – 65 Hz

Power factor: 1

120V single phase: 60 A

120V dual in phase: 60 A total INVERTER

120/240 V split phase: 60 A each leg

9,5 – 17

19 – 33 Output voltage: 120 VAC ± 2%

Frequency: 60 Hz ± 0,1% (1)

38 – 66

5000 4500 4000 10.000 94 25

5000 4500 4000 10.000 94 30 When unit is running in inverter mode, all 240V applications are switched off CHARGER

5000 4500 4000 10.000 95 30

14,4 13,8 13,2 200

28,8 27,6 26,4 120 4 Yes

57,6 55,2 52,8 70

GENERAL

Yes

Yes a–f

Yes

Operating temp.: 0 to 120°F (-20 to +50°C) ENCLOSURE Material & Colour: aluminum (blue RAL 5012)

Humidity (non condensing) : max 95%

Protection category: IP 21

Four M8 bolts (2 plus and 2 minus connections)

Screw terminal 13mm² (AWG 6)

66 lb

30 kg

17,5 x 13,0 x 9,6 inch

444 x 328 x 240 mm

STANDARDS

EN 60335-1, EN 60335-2-29 EN55014-1, EN 61000-3-2 / EN 55014-2, EN 61000-3-3

3) Suitable for parallel, split-phase and 3-phase operation

  • 4)

    At 25 °C ambient

  • 5)

    Non linear load, crest factor 3:1

  • 6)

    Multipurpose relay which can

be

set for general alarm, DC under voltage or genset start signal function

Naam related product Tekst related product

Victron Energy B.V. | De Paal 35 | 1351 JG Almere | The Netherlands General phone: +31 (0)36 535 97 00 | Fax: +31 (0)36 535 97 40 E-mail: sales@victronenergy.com | www.victronenergy.com

Document info
Document views5
Page views5
Page last viewedMon Dec 05 03:45:16 UTC 2016
Pages2
Paragraphs94
Words1147

Comments