X hits on this document

541 views

0 shares

4 downloads

0 comments

109 / 133

109

Allen-Bradley ControlLogix Ethernet Driver Help

Write request for tag '<tag address>' on device '<device name>' failed due to a framing error

Error Type: Warning

Possible Cause: A write request for the specified tag failed after so many retries due to one of the following reasons:

  • 1.

    Incorrect request service code.

  • 2.

    Received more or less bytes than expected.

Solution: If this error occurs frequently, there may be an issue with the cabling or device. Increasing the Retry Attempts will also give the driver more opportunities to recover from this error.

Project Synchronization Errors

Project synchronization is required for the Logical Protocol Modes. Without it, the driver does not have the information necessary to perform Logical reads/writes. Each error below is preceded with the following:

"The following error(s) occurred uploading controller project from device '<device name>'. Resorting to symbolic addressing."

Project Synchronization Errors Encapsulation error occurred while uploading project information. [Encap. Error=<code>] Error occurred while uploading project information. [CIP Error=<code>, Ext. Error=<code>] Framing error occurred while uploading project information Invalid or corrupt controller project detected while synchronizing. Synchronization will be retried shortly Low memory resources Project download detected while synchronizing. Synchronization will be retried shortly Unable to read '<element>' element(s) starting at '<address>' on device '<device name>'. Native Tag size mismatch Unable to read tag '<tag name>' on device '<device name>'. Native Tag size mismatch Unable to write to tag '<tag name>' on device '<device name>'. Native Tag size mismatch

Encapsulation error occurred while uploading project information. [Encap. Error=<code>]

Error Type: Warning

Possible Cause:

The device returned an error within the Encapsulation portion of the Ethernet/IP packet while uploading the controller project.

Solution: The solution depends on the error code that is returned. If the problem persists, contact Technical Support.

Note: A project upload is required for the Logical Addressing Modes.

See Also: Encapsulation Error Codes

Error occurred while uploading project information. [CIP Error=<code>, Ext. Error=<code>]

Error Type: Warning

Possible Cause:

www. kepware.com