Allen-Bradley ControlLogix Ethernet Driver Help

110

The device returned an error within the CIP portion of the Ethernet/IP packet while uploading the controller project.

Solution: The solution depends on the error code that is returned. If the problem persists, contact Technical Support.

Note: A project upload is required for the Logical Addressing Modes.

See Also: CIP Error Codes

Framing error occurred while uploading project information

Error Type: Warning

Possible Cause:

  • 1.

    The packets are misaligned (due to connection/disconnection between the PC and device).

  • 2.

    There is bad cabling connecting the device that is causing noise.

Solution:

  • 1.

    Place the device on a less noisy network.

  • 2.

    Increase the request timeout and/or attempts.

  • 3.

    Restart the server and try again.

Note: A project upload is required for the Logical Addressing Modes.

Invalid or corrupt controller project detected while synchronizing. Synchronization will be retried shortly

Error Type: Warning

Possible Cause: An invalid or corrupt controller project was detected during synchronization.

Solution: No action is required. The driver will re-attempt synchronization after a period of 30 seconds.

Note: Project synchronization is required for the Logical Addressing Modes.

Low memory resources

Error Type: Warning

Possible Cause: Memory required for controller project upload could not be allocated.

Solution:

Close any unused applications and/or increase the amount of virtual memory. Then, restart the server and try again.

Note: A project upload is required for the Logical Addressing Modes.

Project download detected while synchronizing. Synchronization will be retried shortly

Error Type: Warning