X hits on this document

583 views

0 shares

4 downloads

0 comments

112 / 133

Allen-Bradley ControlLogix Ethernet Driver Help

112

Device '<device name>' is not responding. Local node responded with error ' [DF1 STS=<value>]'

Error Type: Warning

Possible Cause:

This error means that the PLC did not respond to the read request from the local node. A local node could be an intermediate node like 1756-DHRIO, 1756-CNB, 1761-NET-ENI, and so forth.

Solution:

Refer to A-B documentation for STS error code definitions. For example, if STS code '0x02'(hex) is returned, verify the cabling between the remote node (PLC) and the local node.

Unable to read '<block size>' element(s) starting at '<address>' on device '<device name>'. [DF1 STS=<value>, EXT STS=<value>]. Tag(s) deactivated

Error Type: Warning

Possible Cause: The address requested in the block does not exist in the PLC.

Solution:

Check the status and extended status codes that are being returned by the PLC. An extended status code may not always be returned; therefore, the error information is contained within the status code. The codes are displayed in hexadecimal.

Status code errors in the low nibble of the status code indicate errors found by the local node. The driver will continue to retry reading these blocks of data periodically. Errors found by the local node occur when the KF module cannot see the destination PLC on the network.

Status code errors in the high nibble of the status code indicate errors found by the PLC. These errors are generated when either the block of data the driver is asking for is not available in the PLC or the address does not exist in the PLC. The driver will not ask for these blocks again after receiving this kind of error.

Note:

The block starting at address <address> may be deactivated in the process depending on the severity of the error.

See Also: A-B documentation for STS and Ext. STS error code definitions.

Unable to read '<block size>' element(s) starting at '<address>' on device '<device name>'. Frame received contains errors

Error Type: Warning

The Error Could Be:

  • 1.

    Incorrect frame size received.

  • 2.

    TNS mismatch.

  • 3.

    Invalid response command returned from device.

Possible Cause:

  • 1.

    Misalignment of packets due to connection/disconnection between PC and device.

  • 2.

    There is bad cabling connecting the devices that is causing noise.

Solution:

The driver will recover from this error without intervention. If this error occurs frequently, there may be an issue with the cabling or the device itself.