Allen-Bradley ControlLogix Ethernet Driver Help

Database Error: Data type for Ref. Tag '<tag name>' unknown. Setting Alias Tag '<tag name>' data type to Default ('<type>')

Error Type: Warning

Possible Cause:

The data type of the "Alias For" *tag referenced in the Alias Tag's declaration could not found in the Tag Import file. This data type is necessary to generate the alias tag correctly.

Solution: The Alias Tag will take on the default type specified in the Default Type tab in Device Properties.

Note:

In RSLogix5000, "Alias For" is a column in the tag view under the Edit Tags tab. This is where the reference to the tag, structure tag member, or bit that the alias tag will represent is entered.

See Also: Logix Options

Database Error: Error occurred processing Alias Tag '<tag name>'. Tag not added

Error Type: Warning

Possible Cause: An internal error occurred processing alias tag <tag name>. Alias tag could not be generated.

Solution: None.

Database Error: Member data type '<type>' for UDT '<UDT name>' not found in Tag Import file. Setting to Default Type '<type>'

Error Type: Warning

Possible Cause:

The definition of data type '<type>', for a member in the user-defined type <UDT name>, could not be found in the Tag Import file.

Solution: This member will take on the default type specified in the Default Type tab of Device Properties.

See Also: Logix Options

Database Error: Program group '<orig. program name>' exceeds 31 characters. Program group renamed to '<new program name>'

Error Type: Warning

Possible Cause:

The program name assigned to this group exceeds the 31 character limitation and will be renamed to one that is valid.

Solution: None.

See Also: Controller-to-Server Name Conversions