Allen-Bradley ControlLogix Ethernet Driver Help

116

Database Error: Tag '<orig. tag name>' exceeds 31 characters. Tag renamed to '<new tag name>'

Error Type: Warning

Possible Cause:

The name assigned to a tag originates from the tag name in the controller. This name exceeds the 31 character limitation and will be renamed to one that is valid.

Solution: None.

See Also: Controller-to-Server Name Conversions

Database Error: Unable to resolve CIP data type '<hex value>' for tag '<tag name>'. Setting to Default Type '<logix data type>'

Error Type: Warning

Possible Cause:

  • 1.

    The CIP data type in the import file is unknown.

  • 2.

    The import file may contain an error.

Solution: Resolve any errors in RSLogix. Then, retry the tag export process in order to produce a new tag import file.

See Also: Preparing for Automatic Tag Database Generation

Invalid or corrupt controller project detected while synchronizing. Try again later

Error Type: Warning

Possible Cause: An invalid or corrupt controller project was detected during synchronization.

Solution: Wait for the project download to complete, and then attempt automatic tag generation.

Project download detected while synchronizing. Try again later

Error Type: Warning

Possible Cause: A project download was attempted while the device was synchronizing with the controller project.

Solution: Wait for the project download to complete, and then attempt automatic tag generation.

Unable to generate a tag database for device <device name>. Reason: Import file not found

Error Type: Warning

Possible Cause: The file specified as the Tag Import File in the Database Settings tab of Device Properties cannot be found.