All reads and writes in progress halt and fail.

l

The controller is polled every 2 seconds to monitor for project change completion.

l

The project change is no longer detected.

l

A message is posted to the Event Log indicating that a change is no longer detected.

During project change, the scenario for online and offline edits is as follows:

l

The response data is ignored.

l

All reads and writes in progress are retried.

121

4.

Allen-Bradley ControlLogix Ethernet Driver Help

5. The reads and writes resume using Symbolic Mode.

Project Change Procedure (Logical Modes)

  • 1.

    A project change is detected.

  • 2.

    A message is posted to the Event Log indicating that a change is detected.

  • 3.

    During project change, the scenario for downloads is as follows:

l

All reads and writes in progress halt and fail.

l

The controller is polled every 2 seconds to monitor for project change completion.

l

The project change is no longer detected.

l

A message is posted to the Event Log indicating that the change is no longer detected.

4.

During project change, the scenario for online and offline edits is as follows:

l

The response data is ignored.

l

All reads and writes in progress are retried.

  • 5.

    The reads and writes resume using Symbolic Mode.

  • 6.

    If the Synchronize with Controller options are enabled:

l

After 30 seconds of Symbolic Mode, the driver uploads (synchronizes) the project from the controller.

l

The reads and writes resume using Logical Mode with the new logical addresses.

7.

If the Synchronize with Controller options are disabled, the reads and writes resume using Logical Mode with the old logical addresses.

SoftLogix 5800 Connection Notes

For proper operation, no Ethernet-based drivers (such as ethernet devices, remote devices via Gateway, and so forth) should be installed in RSLinx on the SoftLogix PC. With one or more Ethernet-based drivers installed, requests will return with CIP Error 0x5 Ext. Error 0x1 and CIP Error 0x8.

Connecting to a SoftLogix Soft PLC on the Same PC as the OPC Server

To connect the Allen-Bradley ControlLogix Ethernet Driver to a SoftLogix Soft PLC running on the same PC as the server, follow the instructions below.

  • 1.

    Ensure that there are no Ethernet-based drivers currently running in RSLinx on the PC.

  • 2.

    Verify that the Ethernet/IP Message Module is installed in the SoftLogix virtual chassis.

  • 3.

    Open the server's Device Propeties. In the General tab, locate the Device ID value. It should not be

" 1 2 7 . 0 . 0 . 1 , 1 , < P L C _ C P U _ s l o t > " . T h e D e v i c e I D s h o u l d b e s e t t o " < s p e c i f i c _ I P _ a d d r e s s _ o f _ <PLC_CPU_slot>". P C > , 1 ,