2 Assessment of fitness for use

2.1 Meaning of "fitness for use"

See Part 1 – "General"

2.2 Elements of the assessment of fitness for use

See Part 1 – "General"

2.3 Relationship of requirements to the product characteristics and methods of verification and assessment

The product characteristics, methods of verification and assessment criteria which are relevant for the fitness of Fire Stopping and Fire Sealing Products for the intended use referred to in 1.2 are given in Table 1 of Part 1 – "General" and apply except where modified or specified below.

Table 1 - Product characteristics and methods of verification and assessment

Nr

Product characteristic

Option "No Performance Determined"

Method of verification and assessment

Expression of product performance

Essential Requirement 1:  Mechanical resistance and stability

None

Essential Requirement 2:  Safety in case of fire

1

Reaction to fire

Permitted: class F according to EN 13501-1

2.4.1

Classes A1-F according to EN 13501-1

2

Resistance to fire

4.2.3 Limitation of generation and spread of fire and smoke within construction works

Not permitted

2.4.2

Classification according to EN 13501-2

Essential Requirement 3:  Hygiene, health and environment

3

Air permeability (material property)

Permitted

2.4.3

Declared value

4

Water permeability (material property)

Permitted

2.4.4

Pass / fail

5

Release of dangerous substances

NOT permitted

2.4.5

Indication of dangerous substances or “Nodangerous substances”4

Essential Requirement 4:  Safety in use

6

Mechanical resistance and stability

Permitted

2.4.6

See 2.4.6

7

Resistance to impact/movement

Permitted

2.4.7

Zone type according to EOTA TR 001

8

Adhesion *)

Permitted

2.4.8

See 2.4.8

Essential Requirement 5:  Protection against noise

9

Airborne sound insulation

Permitted

2.4.9

Single number rating

Essential Requirement 6:  Energy economy and heat retention

10

Thermal properties

Permitted

2.4.10

Declared value

11

Water vapour permeability **)

Permitted

2.4.11

Declared value

General aspects relating to fitness for use ***)

12

Durability and serviceability

Not permitted

2.4.12

Use category regarding environmental conditions

4 EU data base see: www.Europa.eu.int/comm/enterprise/construction/internal/dangsub/dangmain.htm