Wraps (integrated into a wall or floor) including strips and composite strips

Mechanically actuated systems

Putties

Sand gaskets

Sealants/Mastics

Combinations of the products named above

A penetration seal may contain either one type of the services listed in chapter 1.2, (1)-(7), or different types. The number of services is variable.

1.2 Intended use of the construction product

This ETAG shall be used to deliver European Technical Approvals for products intended to be used as penetration seals, which are used to maintain the fire resistance of a separating element at the position where services pass through.

This ETAG covers products intended to be penetrated by the following services (exhaustive list):

(1)cables (single or bundled)

(2)bus bars

(3)pipes and conduits of reaction to fire class A1 according to EN 13501-1 with a melting or decomposition point greater than 1000°C (e.g. steel, cast iron, copper and copper alloys, nickel alloys), either insulated or non-insulated, hereafter referred to as "metal pipes". Included in this group are the above pipes with a coating provided the overall reaction to fire class is minimum A2.

(4)trunking of reaction to fire class A1 according to EN 13501-1 with a melting or decomposition point greater than 1000°C. Included in this group are the above trunkings with a coating provided the overall reaction to fire class is minimum A2.