X hits on this document

35 views

0 shares

0 downloads

0 comments

10 / 16

Magnetic Field: ANSI C12.1

EFT/B: IEC 61000-4-4: level 4—4kV AC lines and 2kV I/O and COM lines

SWC: IEEE/ANSI C37.90.1—2.5kV—measuring inputs, I/O and COM

ESD: IEC 61000-4-2: level 4—15kV air discharge

Radiation Susceptibility: ANSI C12.1

RADIO FREQUENCY EMISSION

Radiation and Conducted emission: CFR47/FCC p.15 class B

Construction, FORM 9S/A

According to ANSI C12.1, ANSI C12.10

SAFETY

UL/CSA 61010-1: 2006

INSULATION

Insulation: ANSI C12.1—2.5kV AC @ 1mn

Standards Compliance Specifications

ACCURACY

  • ANSI C12.20: Class 10/20: 0.2S

  • IEC 62053-22: Class 0.2S

POWER QUALITY

  • Harmonics and interharmonics measurement: IEC 61000-4-7

class I

  • Flicker measurement: IEC 61000-4-15

  • Power quality measurement methods: IEC 61000-4-30 class A/

EN 50160

  • Real-time clock backup and accuracy: IEC 61038

POWER CONSUMPTION

  • 5W or 20VA on each voltage input: ANSI C12.1-2008

EMC IMMUNITY AC Line Surge: IEEE/ANSI C62.41-2002 100kHz ring wave @ 6kV/0.5kA 1.2/50 μs – 8/20 μs Impulse @ 6kV / 3kA