Technical Specifications

Operating Temperature range

-40°C to + 85°C

Rated Input, 0-70 Hz

50-288V AC, 90-290V DC

Isolation

2500V AC @ 1mn

Output voltage

+12V DC ± 5%

Output power

7.5W maximum

Terminals for wires size

2 x 2.5 mm2 pig-tail cable

Operating Temperature range

-40°C to + 85°C

Rated Input

18.5-58V DC

Insulation Dielectric withstand

3000V DC @ 1mn

Output voltage

+12V DC ± 5%

Output power

7.5W maximum

Terminals for wires size

2 x 2.5 mm2 pig-tail cable

Minimum operation reserve 48 h.—if no use of battery (According to AS 1284.7/IEC 1038)

Total reserve capacity shall be not less than 2000h—with use of battery. (According to AS 1284.7/IEC 1038)

More than 10 years service battery life (According to AS 1284.7/ IEC 1038)

Operational temperature

-40°C to 75°C

Optional LCD Operational temperature

-20°C to 70°C

Storage temperature

-40°C to 85°C

Auxiliary AC/DC Power Supply

AC/DC Optional module

24/48 VDC (Phase II) Optional module (future option)

Battery for RTC and SRAM

Environment Temperature

320x240 dots resolution

2 x RED (WATT & VAR)

ANSI C12.18

2

1

1

1

16 MB

57.73-120V AC ± 20%

2500V AC @ 1mn

  • -

    40°C to + 85°C

+12V DC ± 5%

7.5W maximum

120-277V AC ± 20%

2500V AC @ 1mn

  • -

    40°C to +85°C

+12V DC ± 5%

7.5W maximum

Meter Shop Installable

Display Unit

4" Graphic LCD Display

Energy LED Pulsing

IR port

Accessible Buttons—SCROLL, SELECT/ENTER

Sealed Button—DEMAND RESET

Under cover Button—TEST mode

Low Voltage (standard)

Three Phase PS, Rated Inputs 50/60 Hz

Insulation Dielectric withstand

High Voltage (future option)

Operating Temperature range

Output voltage

Output power

Three Phase PS, Rated Inputs 50/60 Hz

Insulation Dielectric withstand

Operating Temperature range

Output voltage

Output power

Real-Time Clock Non-Volatile Memory

Programmable RTC, Error per month <15 s

For energy and tariff registers logging, EV-PQ-DATA-WV log

Power Supply

Supplied from monitored voltage inputs