CITY OF FORT LAUDERDALE

Page

10

AGENDA CODE ENFORCEMENT BOARD CITY COMMISSION MEETING ROOM - CITY HALL NOVEMBER 26, 2002 10:00 AM

THE DEPTH OF THE ELECTRICAL PVC CONDUITS THAT SUPPLY POWER TO THE POWER PEDESTALS IS MUCH LESS THAN THE REQUIRED 18". ALSO THE STREET LIGHTING CABLING IS NOT BURIED TO THE PROPER DEPTH.

NEC 339-3(b)9

COMPLIED

THE CABLE USED FOR THE STREET LIGHTING AND ADDED FEEDERS TO MOBILE HOMES AT SITES 615, 616, 713, AND 817 IS BEING EXPOSED TO DIRECT SUNLIGHT.

NEC 550-23(f) ALL THE POWER PEDESTALS FOR MOBILE HOMES ARE MOUNTED TOO LOW

NEC 550-24(b) THE ALTERATIONS TO THE 60 AMP ELECTRIC SERVICE SYSTEMS HAVE TRIGGERED THE REQUIREMENTS TO UPGRADE THESE SYSTEMS TO 100 AMPS. THE REPLACEMENT CONDUCTORS THEREFORE DO NOT MEET THESE REQUIREMENTS.

NEC 550-5(a)

COMPLIED

THE MOBILE HOMES OWNED BY SUNSET COLONY MOBILE HOME PARK AT SITES 615, 616, 713, AND 817 HAVE SEVERAL ELECTRICAL CABLES

SUPPLYING POWER TO THEM, INSTEAD OF JUST ONE

CODE.

ALSO THESE

EXTRA

CABLES

ARE

NOT

RATED

AS REQUIRED FOR THIS

BY

APPLICATION.

NFPA 501A 4-2.1.1

THE REQUIRED DISTANCE SEPARATION OF 6 FEET PROVIDED BETWEEN SITES 924 & 925 AND 616 & REQUIRED DISTANCE SEPARATION OF 10 FEET IS

IS NOT BEING 603. THE NOT PROVIDED

BETWEEN SITES 705 & 706 AND 714 & 715.

SEPARATION

VIOLATIONS

MAY

NOT

BE

LIMITED

THE

TO

DISTANCE THESE LOCATIONS.

NFPA 501D 4-4.1

THE DISTANCE REQUIRED FOR ACCESSORY STRUCTURES TO BE LOCATED

RELATIVE TO THE SITE SEPARATION

BEING

MAINTAINED.

AN

ACCESSORY

LINES OF THE PARK IS NOT STRUCTURE CONSTRUCTED OF

COMBUSTIBLES IS LOCATED ON THE

AND 811. SITES 904

ACCESSORY STRUCTURES & 905, 921 & 922 AND

SEPARATION

VIOLATIONS

MAY

NOT

SITE LINE CROSS THE SITES 915

BE

LIMITED

BETWEEN SITE 810 SITE LINES BETWEEN & 916. THE DISTANCE TO THESE LOCATIONS.

SFBC 2303.1(a) THE SYSTEM OF REPAIR (see "to wit" for section 105.1(a) for description in detail) EMPLOYED FOR THE REPAIR OF THE SERVICE DROP/METER BANK SUPPORT STRUCTURES IS CONTRARY TO SOUND ENGINEERING PRACTICES.

5211.2(g)(2)(gg) THE REQUIRED 20' WIDE ACCESS ROAD IS NOT BEING PROVIDED.

---------- CASE NO: CASE ADDR: OWNER: INSPECTOR:

---------------------------------------------------------------------- CE00080137 3001 STATE ROAD 84 NEW RIVER BOAT CLUB INC WAYNE STRAWN **REQUESTING EXTENSION OF TIME**

VIOLATIONS:

15-28

COMPLIED