CITY OF FORT LAUDERDALE

Page

13

AGENDA CODE ENFORCEMENT BOARD CITY COMMISSION MEETING ROOM - CITY HALL NOVEMBER 26, 2002 10:00 AM

  • 2.

    SUPPORT STRUCTURES FOR THE SERVICE METER BANKS ARE RUSTED OUT/THROUGH AND PREVIOUS ATTEMPTS TO REPAIR THEM INSTEAD OF REPLACING THEM HAVE BEEN UNACCEPTABLE.

  • 3.

    THE REQUIRED BURIAL DEPTH FOR CONDUIT AND UNDERGROUND CABLE HAS NOT BEEN PROVIDED AT THE FOLLOWING LOCATIONS:

    • A.

      THE FEEDER CONDUITS TO SUPPLY POWER FROM METER BANKS TO INDIVIDUAL PEDESTALS.

    • B.

      THE FEEDER CABLES TO POWER STREET LIGHTING POLES.

    • C.

      CONDUIT ADJACENT TO THE SHUFFLEBOARD COURTS IS INSTALLED ON THE SURFACE OF THE SLAB.

  • 4.

    FEEDER CONDUCTORS TO POWER PEDESTALS FOR MOBLIE HOME POWER HAVE BEEN INSTALLED WITH INSUFFICIENT AMPACITY (WIRE SIZE LESS THAN REQUIRED).

  • 5.

    POWER PEDESTALS HAVE BEEN INSTALLED AT BELOW THE REQUIRED HEIGHT.

  • 6.

    STREET LIGHTING AND COURTYARD LIGHTING HAVE BEEN INSTALLED USING IMPROPER MATERIALS SUCH AS PLUMBING FITTINGS . THE LOCATION OF THIS LIGHTING IS ADJACENT TO THE FOLLOWING SITES: 320, 418, 503, 119, AND 105. COURTYARD LIGHTING IS FOUND FOR THE COURT YARD ADJACENT TO SITE 101 AND FOR THE SHUFFLEBOARD COURTS ON THE NORTHEAST OF THE PARK.

  • 7.

    THE METER BANK ADJACENT TO THE MOBILE HOME AT SITE #1005 IS TOO CLOSE TO THE MOBILE HOME AND DOES NOT HAVE SUFFICIENT WORKING CLEARANCE.

4505.1(a) COMPLIED

THE INSTALLATION OF WIRING AND EQUIPMENT HAS BEEN DONE WITHOUT OBTAINING PERMITS. THE WORK INCLUDES:

  • 1.

    FEEDER CONDUITS AND WIRING FROM THE MAIN DISCONNECTS TO THE POWER PEDESTALS INCLUDING THE WIRING OF THE POWER PEDESTALS.

  • 2.

    THE INSTALLATION OF A STREET LIGHTING SYSTEM AND COURT- YARD FLOODLIGHTING INCLUDING LIGHT POLES, UNDERGROUND WIRING, JUNCTION BOXES AND TIE-INS.

  • 3.

    THE ALTERATION OF THE ELECTRICAL SYSTEM OF MOBILE HOMES

OWNED BY SUNSET COLONY MOBILE HOME PARK. THE MOBILE HOMES WHICH HAVE BEEN ALTERED ELECTRICALLY INCLUDE

SITE:

105, 513, 1004, AND 210.

4.

INSTALLATION

OF

LIGHTING

FOR

THE

SIGNS

LOCATED

AT

5.

THE ENTRANCE TO THE PARK. UNDERGROUND CONDUIT AND FEEDERS TO ALONG WITH PREMISE WIRING OF GUARD

POWER GUARD SHACK.

SHACK

NEC 110-26(a)1 SAFE WORKING SPACE OF THREE FEET IN FRONT OF THE ELECTRIC METER BANK AT SITE 1005 IS NOT BEING PROVIDED.

NEC 240-3(d)

COMPLIED

MULTIPLE CABLES FROM THE POWER PEDESTAL BEING UTILIZED TO SUPPLY POWER TO THE MOBILE HOMES OWNED BY SUNSET COLONY MOBILE HOME PARK DO NOT HAVE THE PROPER OVERCURRENT PROTECTION. THESE ARE LOCATED AT THE FOLLOWING SITES: 1004, 105, 210, AND 513.

NEC 300-15(a)

COMPLIED

PLUMBING FITTINGS AND OTHER SUB-STANDARD MATERIALS ARE BEING USED FOR THE STREET LIGHTING AND THE FLOODLIGHTING