---------- CASE NO: CASE ADDR: OWNER: INSPECTOR:

VIOLATIONS

CITY OF FORT LAUDERDALE

Page

14

AGENDA CODE ENFORCEMENT BOARD CITY COMMISSION MEETING ROOM - CITY HALL NOVEMBER 26, 2002 10:00 AM

SYSTEM IN THE COURTYARDS OF THE PARK.

NEC 300-5(a) THE CONDUIT UTILIZED FOR THE CONNECTIONS FROM THE METER BANKS TO PEDESTALS ALONG WITH THAT WHICH HAS BEEN INSTALLED FOR STREET LIGHTING AND COURTYARD LIGHTING HAS NOT BEEN BURIED TO THE REQUIRED DEPTHS.

NEC 339-3(b)9

COMPLIED

CABLING BEING UTILIZED FOR STREET LIGHTING AND FOR POWER SUPPLY FROM PEDESTALS TO MOBILE HOMES OWNED BY SUNSET COLONY MOBILE HOME PARK IS BEING EXPOSED TO DIRECT SUNLIGHT AND IS NOT DESIGNED FOR THIS PURPOSE. SOME OF THE MOBILE HOMES ARE LOCATED SITES 105,1004, 210 AND 513.

NEC 550-23(f) ALL THE POWER PEDESTALS WHICH HAVE BEEN INSTALLED WITHOUT PERMITS HAVE BEEN MOUNTED TOO LOW. THIS INCLUDEDS APPROXIMATELY 124 OF THE 145 PEDESTALS IN THIS AREA OF THE PARK.

NEC 550-24(b) THE ALTERATIONS TO THE EXISTING 60 AMP ELECTRIC SERVICE SYSTEMS HAVE TRIGGERED THE REQUIREMENT TO UPGRADE THE SYSTEMS TO 100 AMPS. THE REPLACEMENT CONDUCTORS INSTALLED WITHOUT PERMITS DID NOT ADHERE TO THE UPGRADE REQUIREMENT THEREFORE DO NOT MEET THE SIZING REQUIREMENTS. THIS ENCOMPASSES APPROXIMATELY 124 OF THE 145 PEDESTALS LOCATED IN THIS AREA OF THE PARK.

NFPA 501A 4-2.1.1 THE MOBILE HOMES LOCATED AT THE FOLLOWING SITES DO NOT HAVE THE REQUIRED DISTANCE SEPARATION: 312, 325, 304, 305, 221, 222, 413, 426, 414, 401, 318, 405, 418, 209, 210, 313, 315, AND 314.

SFBC 2303.1(a) THE SYSTEMS OF REPAIR EMPLOYED TO REPAIR THE SUPPORT STRUCTURES FOR THE METER BANKS IS CONTRARY TO SOUND ENGINEERING PRACTICES AND THE WELDING THAT HAS BEEN UTILIZED HAS NOT BEEN PERFORMED BY A CERTIFIED WELDER AS REQUIRED.

---------------------------------------------------------------------- CE01081572 350 SW 27 AV CLARKSON-BERGMAN FAM PRTNR LTD WAYNE STRAWN **REQUESTING EXTENSION OF TIME**

:

105.1(a)

THE MOBILE HOME AT SITE 1616 IS NOT PROPERLY SECURED TO PREVENT TOPPLING IN A WINDSTORM. NO SAFEGUARDS ARE PROVIDED FOR THE DOORWAYS WHICH EXIT THE DWELLING ON THE EAST AND NORTH EXPOSURES. PERSONS EXITING THE DWELLING ARE NOT PROTECTED FROM A FALL. THE ROOFING MATERIAL FOR THE ADDITION ON THE NORTH IS NOT FASTENED PROPERLY AND MAY BECOME FLYING DEBRIS IN A WINDSTORM.