CITY OF FORT LAUDERDALE

Page

15

AGENDA CODE ENFORCEMENT BOARD CITY COMMISSION MEETING ROOM - CITY HALL NOVEMBER 26, 2002 10:00 AM

301(a) THE MOBILE AT SITE 1616 HAS BEEN INSTALLED WITHOUT A PERMIT. THE ADDITION TO THE MOBILE HOME ON THE NORTH HAS BEEN BUILT WITHOUT A PERMIT.

301.1(k) AIR CONDITIONERS HAVE BEEN ADDED TO THE MOBILE HOME AT SITE 1616 WITHOUT OBTAINING PERMITS.

4501.2(d) STEEL CONDUITS ARE RUSTED OFF OR THROUGH EXPOSING THE CONDUCTORS TO PHYSICAL DAMAGE. THESE ARE LOCATED AT METER STANCHIONS WHICH SERVE THE FOLLOWING SITES: 1808,1515,1505, 1705,1715,1804, AND 1812.

    • 4505.1

      (a) COMPLIED THE INSTALLATION OF ELECTRICAL EQUIPMENT AND WIRING HAS BEEN DONE WITHOUT OBTAINING THE REQUIRED PERMIT. THE WORK INCLUDES:

    • 1.

      THE INSTALLATION OF A STREET LIGHTING SYSTEM INCLUDING MASTS, UNDERGROUND WIRING, JUNCTION BOXES AND TIE-INS.

    • 2.

      THE INSTALLATION OF CIRCUITS FOR EQUIPMENT AND LIGHT FIXTURES IN THE SHELTER BUILDING FOR THE SEWAGE LIFT STATION.

    • 3.

      THE INSTALLATION OF POWER PEDISTALS IN TEH 1400 BLOCK.

47-5.50.C. THE ROOF STRUCTURE WHICH HAS BEEN ADDED TO THE NORTH SIDE OF THE MOBILE HOME AT SITE 1616 EXCEEDS THE 80% OF THE LENGTH OF THE MOBILE HOME PROHIBITION.

NEC 110-13(a) ALL OF THE ELECTRIC POWER PEDESTALS OF THE SITES NUMBERED IN THE FOURTEEN HUNDREDS HAVE BEEN INSTALLED WITHOUT PROPER SUPPORT.

NEC 300-15(a)

COMPLIED

PLUMBING FITTINGS AND VARIOUS OTHER SUB-STANDARD MATERIALS ARE BEING USED FOR THE ELECTRICAL STREET LIGHTING SYSTEM.

NEC 300-5(a) THE DEPTH OF BURIED CABLE FOR THE STREET LIGHTING SYSTEM IS INADEQUATE ALONG WITH THE DEPTH OF CONDUIT CONNECTED TO POWER PEDESTALS FOR MOBILE HOME FEEDS LOCATED IN THE 1400 BLOCKS.

NEC 339-3(b)9

COMPLIED

CABLING USED FOR THE STREET LIGHTING SYSTEM IS BEING EXPOSED TO DIRECT SUNLIGHT.

NEC 346-12(a) THE CONDUIT POWERING METER BANKS ATTACHED VERTICALLY TO WOODEN POWER POLES ADJACENT TO SITES 1413 AND 1407 ARE NOT ADEQUATELY SUPPORTED.

NEC 550-23(f) ALL OF THE ELECTRIC POWER PEDESTALS OF THE SITES NUMBERED IN THE FOURTEEN HUNDREDS HAVE BEEN INSTALLED TO LOW.