AGENDA CODE ENFORCEMENT BOARD CITY COMMISSION MEETING ROOM - CITY HALL NOVEMBER 26, 2002 10:00 AM

SUPPORTS INSTEAD OF REPLACING THEM IS UNACCEPTABLE.

    • 3.

      FEEDER CONDUITS FOR TRAILER POWER AND CABLING FOR STREET LIGHTING ARE NOT INSTALLED AT PROPER BURIAL DEPTH

    • 4.

      FEEDER CONDUCTORS FOR TRAILER POWER ARE INSTALLED WITH INSUFFICIENT AMPACITY. (ELECTRIC WIRES ARE SMALLER THAN THE REQUIRED SIZE).

    • 5.

      ELECTRIC POWER PEDESTALS FOR TRAILER POWER ARE INSTALLED AT IMPROPER HEIGHT.

    • 6.

      STREET LIGHTING ADJACENT TO SITES 901, 903, 514, 519, AND 709 IS INSTALLED WITH IMPROPER MATERIAL. (PLUMBING FITTINGS, ETC).

    • 7.

      MAIN ELECTRICAL SERVICE BANK LOCATED AT THE REAR OF SITE 906 DOES NOT HAVE SUFFICIENT WORKING CLEARANCE. (TOO CLOSE TO ADJACENT TRAILER).

    • 4505.1

      (a)

ELECTRICAL WIRING AND EQUIPMENT HAS BEEN INSTALLED WITHOUT PERMITS. THIS WORK THAT IS UNPERMITTED IS DEEMED UNSAFE BY THE SOUTH FLORIDA BUILDING CODE. THIS INCLUDES BUT IS NOT LIMITED TO:

  • 1.

    ELECTRICAL FEEDER CONDUITS AND WIRING FROM THE MAIN DISCONNECTS TO THE POWER PEDESTALS, INCLUDING THE POWER PEDESTALS. (THE POWER PEDESTALS ARE ADJACENT TO EACH TRAILER SITE). WHEN THIS PART OF THE ELECTRICAL SYSTEM WAS REMODELED, EACH TRAILER SITE WAS REQUIRED TO HAVE A 100 AMP RATED SERVICE. THIS REQUIRED UPGRADE WAS NOT PERFORMED.

  • 2.

    ELECTRICAL WIRING FOR THE STREET LIGHTING SYSTEM, WHICH INCLUDES THE UNDERGROUND WIRING, JUNCTION BOXES AND TIE-INS, AND THE LIGHT POLES.

  • 3.

    ELECTRICAL WIRING IN MOBILE HOMES OWNED BY SUNSET COLONY MOBILE HOME PARK LOCATED AT SITES 615, 616, 817, AND 713.

47-34.1 A.

COMPLIED

CONSTRUCTION EQUIPMENT AND MATERIALS IS BEING STORED OUTSIDE BEHIND THE LAUNDRY FACILITY BUILDING ON THE SOUTHEAST PORTION OF THE PROPERTY WHICH IS PROHIBITED IN AN MHP ZONING DISTRICT.

5211.2(g)(2)(ff) COMPLIED

THE REQUIRED HARD SURFACE ACCESS ROAD FOR FIRE EQUIPMENT WEIGHING 32 TONS AND OVER IS NOT BEING PROVIDED.

NEC 110-26(a)1 ADEQUATE SAFE WORKING SPACE OF THREE FEET IN FRONT OF THE ELECTRIC METER BANK AT SITE 906 IS NOT PROVIDED.

NEC 240-3(d)

COMPLIED

ADDITIONAL MULTIPLE CABLES SUPPLYING POWER TO PARK OWNED MOBILE HOMES AT SITES 615, 616, 817, AND 713 DO NOT HAVE PROPER OVERCURRENT PROTECTION.

NEC 300-15(a)

COMPLIED

PLUMBING FITTINGS AND VARIOUS OTHER SUB-STANDARD MATERIALS ARE BEING USED FOR THE ELECTRICAL STREET LIGHTING SYSTEM.