Display and print time scales Data format Protocol used for Recorder Communications

From 3.5 ms/cm to 1.15 month/cm Honeywell proprietary binary encryption

TrendServer Software utilizes the Honeywell Trendbus communication protocol for real time network communications with the V5 recorders. The X Series recorders use the Modbus protocol only.


The Comms Server is a MODBUS master. It has no slave capability. The maximum speed of data transfer over MODBUS is 1 (one) reading per second. The maximum speed of data logging of realtime MODBUS data is 1 (one) reading per second.

OPC Capability

Optional OPC Server broadcasting, for each pen: Current Value; Engineering units; Zero; span; High EU; low EU; for communication with HMI software that supports an OPC Client V2.

Time Synchronisation

For Honeywell recorders connected in Real-time mode with Trendbus, every 5 min- utes for V5 recorders; For FTP transfer, at the end of each scheduled download. The recorders clocks are synchronised to the PC clock.

Software License (Users)

Available as a Single or Five User license, the license is based on the number of PC’s the software is installed on, not the number of users using a particular PC with the software installed on it

Data Import Capability

Provides ability to import data files from many Honeywell Recorders, see “Trend- Manager Pro Features” on page 3.


Databases can be local (on same PC as TrendManager Suite), remote (on different PC), allows the data to be available to other Trend Server Pro users

Password (TrendManager Suite)

Five levels of users – Guest or Default User, Basic User, Standard User, Power User or Administrator, Eight area of access with ability to password protect functions within these areas – Graphing, Folders, Recorders, Database, Server, Import, Communica- tions and Settings. 50 Users with their own password allowed

Audit Manager

Available on TrendServer Pro and is accessed through the password system at the Administrator level, allows the Administrator to configure, log and view all actions that have occurred within the software





Minimum System requirements

For FTP communications and setup transfer

Ethernet port, TCP/IP stack installed, Fixed IP addresses for all connected recorders (FTP transfers available with V5 Recorders, X-Series FTP available soon).

For Real-time communications

Ethernet port, RS485 to RS232 adaptor, TCP/IP stack installed Fixed IP addresses for all connected PCs and recorders

For Database Management Tool

Same as TrendServer Pro. (Microsoft.NET framework needs to be installed) Use with TrendManager software version or higher

Batch Mode

Available with TrendManager Pro and TrendServer Pro only. Use with TrendManager/Server Pro software version or higher

PC Operating System PC System (TrendViewer)

PC System (TrendManager or TrendServer) V5 For RS-485 communications X Series Communications

As for TrendViewer but with: 2 Gbyte Hard-drive free disk space, TCP/IP installed RS-485 or RS-232 port with adapter (V5)

Modbus TCP/IP (slave mode), web over Ethernet (DHCP standard) communications port Modbus RTU (slave mode) via an RS485 port. USB ports allow the use of an ASCII barcode reader.

Supported: Windows™ XP and 2000

1 GHz Pentium processor or higher with a mouse, CD-ROM drive Monitor screen resolution 1024 x 768 minimum requirement, high colour 512 Mbyte of RAM, 50Mbyte free hard disk space 16 colour graphics, 24 bit recommended (Screen Designer only) Flash card reader or USB port for X Series recorders 3.5” floppy disk drive or PCMCIA for V5 recorders