(3)The owner or operator of a municipal waste combustor shall:

(A)install, calibrate, operate, and maintain, for each municipal waste combustor, continuous emission monitors to determine: determine the following:

(i)opacity according to 40 CFR 60.58b(c) for large municipal waste combustors and 40 CFR 60.1720 for class I municipal waste combustors;

(ii)(i)sulfur dioxide emissions, according to 40 CFR 60.58b(e) for large municipal waste combustors and 40 CFR 60.1720 for class I municipal waste combustors;

(iii)(ii)nitrogen oxides emissions, according to 40 CFR 60.58b(h) for large municipal waste combustors and 40 CFR 60.1720 for class I municipal waste combustors; and

(iv)(iii)oxygen or carbon dioxide emissions; according to 40 CFR 60.58b(b) for large municipal waste combustors and 40 CFR 60.1720 for class I municipal waste combustors; and

(v)temperature level in the primary chamber and, where there is a secondary chamber, in the secondary chamber;

(B)monitor the load level of each municipal waste combustor according to 40 CFR 60.58b(i)(6); each class I municipal waste combustor according to 40 CFR 60.1810;

(C)monitor the temperature of each municipal waste combustor the gases flue gases at the inlet of the particulate matter air pollution control device according to 40 CFR 60.58b(i)(7); 60.1815;

(D)monitor carbon feed rate of each municipal waste combustor carbon delivery system and total plant predicted quarterly usage if activated carbon is used to abate dioxins and furans or mercury emissions according to 40 CFR 60.58b(m)(2) and (m)(3); 60.1820

(E)maintain records of the information listed in 40 CFR 60.59b(d)(1) through (d)(15) for large municipal waste combustors and in 40 CFR 60.1840 through 1855 for class I municipal waste combustors for a period of at least five years;

(F)following the initial compliance tests as required under Paragraph (e) of this Rule, submit the information specified in 40 CFR 60.59b(f)(1) through (f)(6) for large municipal waste combustors and in 40 CFR 60.1875 for class I municipal waste combustors, in the initial performance test report;

(F)(G)following the first year of municipal combustor operation, submit an annual report specified in 40 CFR 60.59b(g) for large municipal waste combustors and in 40 CFR 60.1885 for class I municipal waste combustors, as applicable, no later than February 1 of each year following the calendar year in which the data were collected. Once the unit is subject to permitting requirements

under 15A NCAC 02Q .0500, Title V Procedures, the owner or operator of an affected facility shall submit these reports semiannually; and

(H)(G)submit a semiannual report specified in 40 CFR 60.59b(h) for large municipal waste combustors and in 40 CFR 60.1900 for class I municipal waste combustors, for any recorded pollutant or parameter that does not comply with the pollutant or parameter limit specified in this Section, according to the schedule specified in 40 CFR 60.59b(h)(6).

(g)  Excess Emissions and Start-up and Shut-down. All municipal waste combustors subject to this Rule shall comply with Rule .0535, Excess Emissions Reporting and Malfunctions, of this Subchapter.
(h)  Operator Training and Certification.
(1)By January 1, 2000, or six months after the date of start-up of a class I municipal waste combustor, whichever is later, and by July 1, 1999 or six months after the date of start-up of a large municipal waste combustor, whichever is later:
(1)(A)Each chief facility operator and shift supervisor of a municipal waste combustor shall obtain and maintain a current provisional operator certification within six months after he transfers to the municipal waste combustion unit or six months after he is hired to work at the municipal waste combustor unit. from the American Society of Mechanical Engineers (ASME QRO-1-1994).
(2)Each chief facility operator and shift supervisor shall obtain a full certification or be scheduled to take the certification exam within six months after he transfers to the municipal waste combustion unit or six months after he is hired to work at the municipal waste combustor unit.
(3)(B)Each facility operator and shift supervisor of a municipal waste combustor shall have completed full certification exam or shall have scheduled a full certification exam with the American Society of Mechanical Engineers (ASME QRO-1-1994).
(4)(C)The owner or operator of a municipal waste combustor plant shall not allow the facility to be operated at any time unless one of the following persons is on duty at the affected facility:

(A)(i)a fully certified chief facility operator;

(B)(ii)a provisionally certified chief facility operator who is scheduled to take the full certification exam; exam according to the schedule specified in Part (B) of this Subparagraph;

(C)(iii)a fully certified shift supervisor; or

22:23                                                               NORTH CAROLINA REGISTER                                           JUNE 2, 2008