MS116-0.16

1.25 … 1.87

0.16

MS116-0.25

1.95 … 2.92

0.25

MS116-0.4

3.12 … 4.68

0.40

MS116-0.63

4.91 … 7.37

0.63

MS116-1.0

9.20 … 13.8

1.00

MS116-1.6

14.7 … 22.1

1.60

MS116-2.5

23.0 … 34.5

2.50

MS116-4.0

40.0 … 60.0

4.00

MS116-6.3

63.0 … 94.5

6.30

MS116-10

120 … 180

10.0

MS116-12

144 … 216

12.0

MS116-16

192 … 288

16.0

Type

Rated instantaneous short-circuit current setting [A]

Rated operational current [A]

Short-Circuit protection Setting range, short-circuit breaking capacity and max. back-up fuse Maximum rated current of the back-up fuses if lCC > lCS

Setting ranges A…A

ICU kA

230 V AC ICS kA

gG, aM ICU

A

kA

400 V AC ICS kA

gG, aM ICU

A

kA

440 V AC ICS kA

gG, aM ICU

A

kA

500 V AC ICS kA

gG, aM ICU

A

kA

0.10 … 0.16

0.16 0.25 0.40 0.63 1.00 1.60 2.50 4.00 6.30 8.00 1 0 . 0

  • 0.25

  • 0.40

  • 0.63

  • 1.00

  • 1.60

  • 2.50

  • 4.00

  • 6.30

  • 10.0

  • 12.0

1 6 . 0

No back-up fuse required up to lcc

= 50 kA

25

25

80

25

25

80

16

16

80

16

16

80

10 6 6 6 6 4

10 6 6 6 6 4

No back-up fuse required up to lcc

= 30 kA

25

10

10

25

5

25

6

6

25

2

63

6

6

63

2

63

6

6

63

2

63

6

6

63

2

63

4

4

63

2

lCS lCU lCC l CU

= Rated service short-circuit breaking capacity = Rated ultimate short-circuit breaking capacity = Prospective short-circuit current at installation location = lCS in case of MS116

6 Manual motor starter MS116 | Data sheet

ICS

gG, aM

kA

A

690 V AC

5

25

2

25

2

40

2

50

2

50

2

63